Voltage, current, frequency, active power, reactive power, apparent power, active energy, reactive energy, apparent energy, power factor (cos), neutral current, demand, harmonics, quality (swell/dip/interruption, transient/overvoltage, inrush current, unbalance rate) capacitance calculation for PF correction unit, flicker

  1. Simultaneous power and power quality measurements - calculate power, harmonics, waveform and power quality simultaneously
  2. 3 voltage channels and 4 current channels
  3. Helpful support functions - quick start guide, wiring check and sensor detection
  4. Guaranteed high accuracy measurements in compliance with IEC 61000-4-30 Class S and EN50160
  5. Remote monitoring on PC and Android devices - remote checking via Bluetooth communication and store data on the included SD card
  6. Compatible with various clamp sensors with range from 1000mA up to 3000A (plus earth leakage)
  7. Energy consumption check on site with trend and demand graphs
  8. High quality full colour TFT display with high resolution
  9. IEC 61010-1 compliant
  10. CAT IV 300, CAT III 600V and CAT II 1000V rated

Voltage (RMS

Range

600.0/1000V

Accuracy

±0.2% rdg ±0.2% f.s. (sine wave, 40-70Hz)

Allowable Input

1-120% of each range (rms). 200% of each range (peak)

Display Range

0.15 - 130% of each range

Crest Factor

3 or less

Sampling Speed of Voltage Transient

2.4μs

Current (RMS) 

Range

8128 (50A type) :5/50A/AUTO
8127 (100A type) :10/100A/AUTO
8126 (200A type) :20/200A/AUTO
8125 (500A type) :50/500A/AUTO
8124/8130 (1000A type) :100/1000A/AUTO
8146/8147/8148 (10A type) :1/10A/AUTO
8129 (3000A type) :300/1000/3000A

Accuracy

±0.2%rdg±0.2%f.s.+accuracy of clamp sensor (sine wave, 40~70Hz)

Allowable Input

1~110% of each range (rms). 200% of each range (peak)

Display Range

0.15 - 130% of each range

Crest Factor

3 or less

Active Power 

Accuracy

±0.3%rdg±0.2%f.s. + accuracy of clamp sensor (power factor 1, sine wave, 40~70Hz)

Influence of Power Factor

±1.0%rdg (reading at power factor 0.5 against power factor 1)

Other Specs

 Frequency Meter Range

40 to 70Hz

Power Supply

(AC Line)AC100 - 240V/50-60Hz/7VA max

Power Supply

(DC Battery)Alkaline size AA battery LR6 or Ni-MH (HR15-51) x 6
Battery life approx 3h (LR6, backlight off)

Internal Memory

Flash memory (4MB)

PC Card Interface

SD Card (2GB)

PC Communication Interface

USV Ver 2.0, Bluetooth Ver 2.1 + EDR Class 2

Display

320 x 240 (RGB) pixel, 3.5" colour TFT display

Display Update Period

1 sec

Temperature and Humidity Range

23±5℃,less than 85% RH(without condensation)

Operating Temperature and Humidity Range

0~45℃,leaa than 85% RH(without condensation)

Storage Temperature and Humidity Range

-20~60℃,less than 85% RH(without condensation)

Applicable StandardsIEC61010-1 CATⅣ 300V, CATⅢ 600V,
CATⅡ 1000V Pollution degree 2
IEC61010-2-030, IEC61010-031, IEC61326, EN50160
IEC61000-4-30 Class S, IEC61000-4-15, IEC61000-4-7